I have a 4 month old CyberPower (CP 1500PFCRM2U) with a constant load of 190-210w.  Running some tests with proxmox, I discovered the UPS drain incredibly fast: 

Load: 19–20% (about 190–200 W)  
Charge: 100% → 81% in about 65 seconds  
Battery voltage: held steady around 24.1 V**.**  Both battery and charger side read 27.4V.

Is this normal?  Cyberpower will RMA it but I really can’t be without an ups for 2 weeks.  Disappointed with the amount of testing and provided logs they won’t drop ship a replacement first.  Is this performance standard with their units? 
```