UPS drain concern
retained text
I have a 4 month old CyberPower (CP 1500PFCRM2U) with a constant load of 190-210w. Running some tests with proxmox, I discovered the UPS drain incredibly fast: Load: 19–20% (about 190–200 W) Charge: 100% → 81% in about 65 seconds Battery voltage: held steady around 24.1 V**.** Both battery and charger side read 27.4V. Is this normal? Cyberpower will RMA it but I really can’t be without an ups for 2 weeks. Disappointed with the amount of testing and provided logs they won’t drop ship a replacement first. Is this performance standard with their units?